Power Factor Correction Kva To Kw
Calculator

Inputs

Real power (kW)
75

Results

Real power (kW)
75
Reactive power before correction (kVAR)
66.143782
Reactive power after correction (kVAR)
24.651307
Required capacitor power (kVAR)
41.492474

Energy results

Real power (kW)75
Reactive power before correction (kVAR)66.143782
Reactive power after correction (kVAR)24.651307
Required capacitor power (kVAR)41.492474

formula-map diagram

Real power (kW)
75
Reactive power before correction (kVAR)
66.143782
Reactive power after correction (kVAR)
24.651307
Required capacitor power (kVAR)
41.492474

Energy relationship

Formula

kW = kVA × PF; kVAR needed = kW × (tan(cos⁻¹PF₁) − tan(cos⁻¹PF₂))

= 75

Note

This is a simplified model: it applies the standard equation to the numbers you entered and ignores real-world losses, weather variation, tariff structures and equipment tolerances. Wind power assumes air density 1.225 kg/m³ at ISA sea level and the power coefficient you enter (Betz limit 0.593). Verify with measured data or a professional energy audit before making purchasing decisions.

Example: with the default inputs, calculator.energy.real_power_kw2 is 75.

More in Energy and environment

See all →

Frequently asked questions

How do I convert kVA to kW?+

Multiply the apparent power in kVA by the power factor. For example, 100 kVA at a power factor of 0.75 gives 75 kW of real power.

How much capacitor capacity do I need to correct the power factor?+

The calculator takes the reactive power before correction, kW times tan(cos⁻¹ of the current power factor), and subtracts the reactive power at the target power factor. The difference is the required capacitor size in kVAR.

What do the current and target power factor mean here?+

The current power factor is what your load has now, and the target is the value you want to reach. The target is capped at 1 in the calculation.

Why does a low power factor matter?+

At the same real power, a lower power factor means more apparent power and more reactive power. This calculator shows that reactive power in kVAR before and after correction.

Is this enough to size a real capacitor bank?+

No, it is an estimate for a single operating point. Have a qualified electrician or engineer size and verify any real installation.