Power Factor Correction Kva To Kw
Calculator

Inputs

Real power (kW)
75

Results

Real power (kW)
75
Reactive power before correction (kVAR)
66.143782
Reactive power after correction (kVAR)
24.651307
Required capacitor power (kVAR)
41.492474

Energy results

Real power (kW)75
Reactive power before correction (kVAR)66.143782
Reactive power after correction (kVAR)24.651307
Required capacitor power (kVAR)41.492474

formula-map diagram

Real power (kW)
75
Reactive power before correction (kVAR)
66.143782
Reactive power after correction (kVAR)
24.651307
Required capacitor power (kVAR)
41.492474

Energy relationship

Formula

kW = kVA × PF; kVAR needed = kW × (tan(cos⁻¹PF₁) − tan(cos⁻¹PF₂))

= 75

Note

This is a simplified model: it applies the standard equation to the numbers you entered and ignores real-world losses, weather variation, tariff structures and equipment tolerances. Wind power assumes air density 1.225 kg/m³ at ISA sea level and the power coefficient you enter (Betz limit 0.593). Verify with measured data or a professional energy audit before making purchasing decisions.